Advanced Gateway Settings

In addition to customizing the Gateway's homepage, there are a number of advanced features in the Gateway that you can customize, such as changing ports, changing the Java version, and changing the allocated memory size.

About Java Versions

Ignition runs on Java, and Java is always being updated to have better security or include new features. It's important to pay attention to what version of Java is being run on the computer that Ignition is installed on, especially since you can have multiple copies of Java on a computer at the same time. We recommend that you turn Java's "Automatic Updates" off since Java will sometimes remove older versions that Ignition might still be using. This is not as important on client computers since you are starting and stopping the clients much less frequently than the Gateway.

You can update which version of Java the Ignition service is pointed to from a configuration file. See Changing Gateway Java Version for more information.

About Memory Usage

The Ignition Gateway uses memory just like any other program, and the amount of memory Ignition is allowed to use can be set in a configuration file. It is important to know how much Ignition initially asks for because if you don't have enough free memory for that initial amount, the Ignition service won't start. Likewise, you can set the maximum memory that Ignition uses so it doesn't starve other programs. Of course we recommend that Ignition is installed on it's own server to it can maximize it's performance, but often Ignition is installed on a computer that is already running several other important programs. Note: on older 32bit systems (modern computers are all 64 bit these days), you cannot set the memory to be more than about 1.5Gb. If you do, the program will never be allowed to start. Learn more about setting memory at Changing Gateway Memory Allocation.

Using Ports

Ignition uses ports on a computer to give you access to the Gateway Webpage. The default port for any webpage is 80, and all webpages hide 80 from you in the website address. If multiple programs try to use the same port they will fail, and because many computers already use this standardized default port, Ignition defaults to 8088 instead. This means that you will access Ignition's gateway webpage with http://ipaddress:8088. Once it is installed, you can change the port Ignition to whatever you like, including to 80. See Changing Gateway Ports.

Port Reference

An Ignition server uses many ports to manage information between itself and other Ignition servers, OPC servers, devices, and other services such as SMTP and ERP servers. The following table describes the default ports an Ignition server may use for communication. Most are configurable and some of these ports may be on a computer other than the one Ignition is installed on (that is, if MySQL is installed on a different computer, the Ignition server will not be using port 3306).

Port
Operation
Protocol
Configurable
Description

8088

Listening

tcp

Yes

Default port setting to access the Ignition gateway

8043

Listening

tcp

Yes

Default SSL port setting to access the Ignition gateway

4096

Listening

tcp

Yes

Default port for OPC-UA server

45900

Listening

tcp

No

Callback port for the mobile module

4445

Outgoing

udp/broadcast

Yes

Default send port for a multicast messaged that makes the gateway discoverable on a local network

4446

Listening

udp/broadcast

Yes

Default receive port for a multicast messages that makes the gateway discoverable on a local network

8750

Listening

tcp

No

Port used for Redundancy/Network Configuration

389

Outgoing

tcp

Yes

Default port for Active directory if this is being used

465

Outgoing

tcp

No

SMTP protocol used if Alarming is configured

5060

Listening

tcp/SIP

No

Send Voice Notification to SIP server

8000

Listening

tcp/RTP

No

Transfer/com for SIP server

17341

Outgoing

tcp

No

Send port for SMS with Alarming

17342

Listening

tcp

No

Receive Port for SMS with Alarming

502

Outgoing

tcp

Yes

Default Modbus port

3306

Outgoing

tcp

Yes

Default MySQL port used for connection

1433

Outgoing

tcp

Yes

Default MSSQL port used for connection

1521

Outgoing

tcp

Yes

Default Oracle port used for connection

50000

Outgoing

tcp

Yes

Default IBM DB2 port used for connection

5432

Outgoing

tcp

Yes

Default Postgresql port used for connection

3050

Outgoing

tcp

Yes

Default Firebirdsql port used for connection

6501

Listening

tcp

No

Server fallback port

5500

Listening

tcp

Yes

Default port for OPC browse of external tags

135

Outgoing

tcp

No

Default port for DCOM communication (old OPCDA servers)