Alarm Properties and Event Reference
General Alarm Properties
-
Go to the Configure section of the Gateway.
-
Choose Alarming > General from the menu on the left.
The General Alarm Settings page is displayed. -
Set the general alarm properties shown in the following table:
Alarm Evaluation |
|
Live Event Limit |
Default is 5. The number of "live" events (active or unacknowledged) that can exist for a single alarm at a given time. When surpassed, older events will be acknowledged automatically by the system. This means as an alarm cycles on and off, Ignition will keep track of the last 5 times the alarm event happened until the user acknowledges them. This does not store history for those events. |
Event Suppression |
|
Continuous Event Detection Window (min) |
Default is 10. The amount of time to store events before shutdown to prevent new duplicate events from being created on startup. This setting prevents unacknowledged active events from being generated due to reboot. If set to 0, will not be used. |
Notify Initial Events |
Default is false. If false, active alarms caused by the "initial state" (that is, the first value checked after being created, or after the enabled state changes) won't be sent to the notification system. This means if you add an alarm to a tag, a notification won't be immediately sent when the new state is created. |
Alarm Properties Table
All alarm states have a list of properties that you can edit or bind when creating or editing a Tag. Here is the list of attributes paired with their scripting names. This is useful when using the system.tag.addTag() and system.tag.editTag() functions.
If the attribute you want to reference is not listed, you can simply change the attribute on your Tag, export it to XML, and view the reference to the alarm attribute.
Property Name |
Scripting Name |
Description |
Main |
||
Name |
name |
The name of the alarm. |
Enabled |
enabled |
Specifies whether or not this alarm is evaluated by the system. |
Priority |
priority |
The priority (or "severity") of this alarm. Diagnostic (0), Low (1), Medium (2), High (3), Critical (4) |
Timestamp Source |
timestampSource |
Dictates whether the timestamp used on the alarm comes from the system or the value. System (0), Value (1) |
Display Path |
displayPath |
An optional path (separated by "/") that will be used for display and browsing purposes. |
Ack Mode |
ackMode |
How acknowledgement works for the alarm: Auto (1) - Alarm is acknowledged when cleared. Manual (2) - Alarm acknowledged by user. Unused (0) - Alarm is always marked as 'acknowledged'. |
Notes |
notes |
Documentation about the alarm. |
Ack Notes Required |
ackNotesReqd |
Select this option to require operators to provide some explanation when the alarm is acknowledged. true or false |
Shelving Allowed |
shelvingAllowed |
true or false |
Alarm Mode Settings |
||
Mode |
mode |
The alarm mode. Each mode has a unique behavior:
Equal (0), Not Equal (1), Above Setpoint (2), Below Setpoint (3), Between Setpoints (4), Outside Setpoints (5), Out of Range (6), Bad Quality (7), Any Change (8), Bit State (9), On Condition (10) |
Setpoint / Low Setpoint |
setpointA |
The value used to initiate an alarm. If the alarm mode calls for two setpoints, this is the low value. |
Inclusive / Low Inclusive |
inclusiveA |
If true, the Setpoint or Low Setpoint value is used inclusively for the condition to alarm. |
High Setpoint |
setpointB |
The high value used to initiate an alarm when the alarm mode calls for two setpoints. |
High Inclusive |
inclusiveB |
If true, the High Setpoint value is used inclusively for the condition to alarm. |
Any Change |
anyChange |
If true, will alarm on each value change given the alarm mode conditions are met. |
Deadbands and Time Delays |
||
Deadband |
deadband |
A numeric deadband of the alarm condition. The interpretation of this value depends on the deadband mode. Note that his deadband is separate from, and evaluated after, the tag's deadband. |
Deadband Mode |
deadbandMode |
Defines how the deadband value is used. If percent, the value (0-100) will be compared against the Eng. limits defined for the value. Absolute (0), Percent (1) |
Active Delay |
timeOnDelaySeconds |
The time, in seconds, before the alarm will be considered truly active after the active condition becomes true. Also known as a "rising edge time deadband". |
Clear Delay |
timeOffDelaySeconds |
The time, in seconds, before the alarm will be considered truly clear after the clear condition becomes true. Also know as a "falling edge time deadband". |
Notification |
||
Active Pipeline |
activePipeline |
The pipeline that will be used to process active events generated by this alarm. |
Clear Pipeline |
clearPipeline |
The pipeline that will be used to process clear events generated by this alarm. |
Ack Pipeline |
ackPipeline |
The pipeline that will be notified when the alarm has been acknowledged. |
Email Notification Properties |
||
Custom Subject |
CustomEmailSubject |
If specified, will be used for the email subject. If blank, the subject defined in the notification block to be used. |
Custom Email |
CustomEmailMessage |
If specified, will be used for email message. If blank,. the message defined in the notification block will be used. |
SMS Notification Properties |
||
Custom Message |
CustomSmsMessage |
If specified, will be used for the SMS message. If blank, the message defined in the notification block will be used. |
Phone Call Settings |
||
Custom Message |
CustomMessage |
If specified, the call will use this message for the alarms. If blank, the message defined on the notification block will be used. |
Associated Data |
||
User Defined Data |
|
|
Alarm Properties
An alarm event is made up of many pieces of information. The state, the value, the time, all of the configuration data for the alarm, and more are collectively known as the properties of the event. A "property" is generally a name, potentially along with a default value. There are many properties that an alarm may have, and if the property isn't present, the default value is usually assumed.
This is different than the alarm properties used during initial setup, these are the properties available when an alarm event occurs (active, clear, acknowledge).
How Properties are Used
Properties are used in a number of ways, they:
-
Define how an alarm behaves.
-
Are referenced in messages, such as the body of an email, or sms message.
-
Are referenced in Expressions, such as in the binding of a different property, or in an Expression block.
-
Are created and used in pipelines as temporary variables, such as to make a counter.
-
... and various other places.
While properties are always accessed the same (for example by using the {propertyName} syntax in a message or Expression, or the getProperty() Expression function), there are some subtle variations on where the property value comes from, and what its lifecycle will be. To understand this better, consider that an Alarm Event has the following structure:
Alarm Event
Active Event Properties
Clear Event Properties
Acknowledged Event Properties
Runtime Properties
The first three collections of properties get created when the described type of event occurs. Consequently, it's possible for the same property to exist multiple times in an Alarm Event. For example, a bound configuration property or associated data is captured on both the active and clear events. When you reference a property, the alarm event will provide you with the most recent value. So, if you have a bound property call "MyData", and you reference it when the alarm is active, you may get a different result than when the reference is executed later and the alarm has cleared. The individual values are stored separately in the alarm journal, however.
Configuration Properties |
|
||||||||||||
Name |
The name of the Alarm. |
||||||||||||
Enabled |
Set to False to turn off the alarm state and all associated actions. |
||||||||||||
Priority |
Used for sorting/filtering. Numerical values are associated with each priority to make comparison easier.
|
||||||||||||
Display Path |
The unique path of the Alarm state. |
||||||||||||
Active Pipeline |
Which pipeline (if any) to use when the alarm goes into the Active State. |
||||||||||||
ClearPipeline |
Which pipeline (if any) to use when the alarm goes into the Clear State. |
||||||||||||
TimeOnDelaySeconds |
The amount of consecutive seconds that the alarm state must be True before the Tag enters this alarm state. |
||||||||||||
TimeOffDelaySeconds |
The amount of consecutive seconds that the alarm state must be False before the Tag exits this alarm state. |
||||||||||||
Notes |
Free-form notes for the alarm state. |
As described in the previous section, Runtime Properties are different in that they only exist while the alarm event is in memory (still "live", that is, not cleared, or not acknowledged). They do not get stored in the alarm journal. In addition to properties created through the Set Property block, the system also has a number of defined Runtime Properties that it may use for various purposes. Though these are used internally, they are technically still regular properties, and can be accessed and modified through the normal means.
Runtime Properties (generated for the event) |
|
IsInitialEvent |
Set to "true" when the event is caused by the initial state of the alarm. |
SystemAck |
Set to "true" when the alarm has been acknowledged by the system, due to an overflow of the "live event queue". Live events are alarm events that are active or not acknowledged, and are limited for each alarm by the general alarm settings. |
ShelfExpiration |
When the shelf will expire for this event. |
IsShelved |
Is the alarm currently shelved? |
EventCanceled |
If set, the event will drop out as soon as possible from the pipelines |
EventId |
The unique id (uuid) of this alarm event. Each event gets a completely unique id. |
Source or Source Path |
The qualified path to the item that generated this event. Includes the Tag Provider, Tag Path, and the name of the alarm. Example: prov:tagProviderName:/tag:folder/tagName:/alm:alarmName |
DisplayPathOrSource |
Gets the display path if defined, otherwise returns the source. |
State |
The current overall state of the alarm: ClearUnacked (0), ClearAcked (1), ActiveUnacked (2), ActiveAcked (3) |
EventState |
The transitional state that caused the current event: Active (0), Clear (1), Ack (2). |
EventValue |
The value associated with the current event. |
AckUser |
The user who acknowledged this event. |
IsAcked |
"True" if the event has been acknowledged. |
IsActive |
"True" if the event is still active. |
IsClear |
"True" if the event is not still active. |
ActiveTime, ClearTime, AckTime |
The timestamp for each event. |
PipelineTransitionCount |
How many transitions the event has made inside of the pipelines. |
Associated Data
You can extend alarm properties by creating your own associated data. Associated data properties can be configured on any alarms that are already configured in a project.
To learn more, refer to Alarm Associated Data.